The Hidden Water Geography of U.S. Hyperscale Data Centers in the AI Era

Water use by data centers is routinely reported as a single footprint, but water is consumed through two physically distinct pathways: at the site for cooling and in the power system that generates electricity. We mapped both pathways for 472 U.S.

Preview
Year
2026
Hosting
Full text hostedCC-BY-4.0

Cite

Notes

Only stored in your browser.

Attribution

Abstract & full text
arxiv.org/abs/2607.02531CC-BY-4.0
TL;DR
Semantic Scholar
Attribution policy →

Abstract

Water use by data centers is routinely reported as a single footprint, but water is consumed through two physically distinct pathways: at the site for cooling and in the power system that generates electricity. We mapped both pathways for 472 U.S. hyperscale facilities by linking facility locations to electricity regions, hydrologic basins, and water-stress data. Under baseline assumptions, operational water consumption totals approximately 300 GL yr^-1 (range 205-451 across scenarios), with electricity-related water contributing three-quarters of the total. The two pathways produce different hotspot geographies: direct cooling burdens concentrate in stressed western and south-central basins, whereas electricity-related burdens concentrate in a few eastern grid regions with fossil-heavy supply. Just 3 of 24 hosting balancing authorities account for 59% of electricity-related water. Separating pathways identifies which decisions matter where: cooling design and water sourcing locally, electricity planning and procurement regionally